Model 10A15-8
Eight-Channel Thermistor Conditioner Card
|
Input Type
|
Description
|
SPS6000
|
SPS8000
|
System 10
|
|
Temperature
|
8-Chn Thermistor
|
X-X
|
X-X
|
X X
|
Within designated ranges, Thermistor Probes offer higher accuracy and greater long-term dependability than thermocouples. Providing regulated excitation current, the Model 10A15-8 can condition up to eight independent temperature signals from many 3-wire, dual-thermistor-bead probes. A variety of suitable fast-response sensors is available in the Daytronic Series 700 Thermistor Temperature Probes (see the latest
Daytronic Transducers Catalog).
Like the Models 10A9-8C and 10A10-4, the Model 10A15-8 provides "absolute" calibration.
Specifications:
- Measurement Range and Resolution: See Table below; automatically selected- on an individual channel basis- when the channel is configured*
- Excitation (per channel): As required for thermolinear transducer
- Amplifier (per channel):
Input Impedance: As required for thermolinear transducer
Offset: Initial: ±0.02% of full scale; vs. Temperature: ±50 ppm/°C; vs. Time: ±20 ppm/month
Gain Accuracy: ±0.02% of full scale (absolute maximum input voltage range without damage is ±9 V
Gain Stability: vs. Temperature: ±50 ppm/°C; vs. Time: ±20 ppm/month
- Filter (per channel): 1-pole modified Butterworth; 3 dB down at 30 Hz; 60 dB down at 100 kHz
Step-Response Settling Time (Full-Scale Output):
To 1% of final value: 30 msec
To 0.1% of final value: 60 msec
To 0.02% of final value: 250 msec
- Total System Accuracy (typical, including Model 10A15-8, probe interchangeability, and system data collection and processing): see Table below
- Auxiliary Outputs: None
*In System 10, all 10A15-8 channels are given a “type” code of “55” and employ a special range/resolution selection procedure.
Thermistor Ranges for the Model 10A15-8
|
Display Resolution
|
Display Resolution
|
Typical System Accuracy*
|
Max. Expected Error*
|
0°C to +100°C
+32°F to +212°F
0°C to +100°C
+32°F to +212°F
|
0.1°C
0.1°F
0.01°C
0.02°F
|
±0.2°C
±0.3°F
±0.2°C
±0.3°F
|
±0.3°C
±0.5°F
±0.3°C
±0.5°F
|
* Including ± one count of least significant digit displayed (i.e., ± 0.1, 0.02, or 0.01) and probe interchangeability error of ±0.15°C or ±0.25°F. (back to top)
|
|