SEARCH

Products
Index

See List

Selection Guide

Applications

Support

Downloads

Reference

Contact Us

HOME

2000 Series
3000 Series
3KPlus Series
3500 Series
4000 Series
5D Series
5M Series
System 10
MeasuringPad
SPS6000
SPS8000
Cards
Transducers
DC Power SYSKON
Software


[Top

    

 

Back to 2000 Series GENERAL PAGE

 

Back to 2000 Series OPTIONS
(Go here to ORDER
THESE PRODUCTS)

 
"A" and "B" Options

Dual Controller Options

The 2000 Series "A" Option provides two Form C, 10-A contact relays (250 V-AC) on a plug-in board.  The "B" Option board provides two Form A opto-isolated AC/DC solid-state relays rated 120 mA at 125 VAC or 250 mA at 150 VDC.

Both options are available for all models, for applications that require alarms and/or process control.  The solid-state version is recommended for high duty cycles and low-level loads.

Either setpoint may be latching or nonlatching.  In the latching mode, when an alarm or shutdown condition is reached, the output remains in the alarm condition until reset via front-panel push buttons, the optional serial interface, or a logic signal received at the rear connector.  In the nonlatching mode, the output is automatically reset as soon as the alarm condition ceases to occur.

 

In NONLATCHING operation, the relay closes when the reading rises above the setpoint and opens when it falls below the setpoint.  Relay ON/OFF control action is independently programmable for each of the two relays and can be reversed through a setup command.

In LATCHING operation, the relay stays actuated until reset externally.  This mode can be used to shut down machinery or a process when an operating limit has been exceeded, or to maintain an alarm until acknowledged by an operator when the alarm condition has passed.

    

Mixed LATCHING and NONLATCHING Relays: One of the relays can operate in a nonlatching mode—for example, to turn off a heater when a temperature setpoint is reached.  Operating as a latching fail-safe backup, the other relay can turn off the entire process when a second, higher setpoint is reached (indicating a malfunction).

Each relay may be separately configured to be energized above or below the setpoint, or may be disabled.  Also, each relay may operate in band deviation or hysteresis mode.

Deviation mode sets up a passband around the setpoint and is often used for component pass-fail testing.  In this mode, an alarm is generated whenever the reading is a specified number of counts above or below the setpoint—for example, to flag an out-of-tolerance condition.

In hysteresis mode, the relay is activated at a specified amount above the setpoint and deactivated at the same amount below the setpoint.  Hysteresis can be used to extend relay contact life by minimizing relay chatter around a setpoint due to signal noise or feedback from load switching.

 

In the above figure, a DEVIATION limit of 50 is set up on each side of the setpoint.  The relay closes (or opens) when the reading falls within the deviation band, and opens (or closes) when it falls outside this band.  This mode establishes a passband around the setpoint, and is often used for component testing.

In the above figure, a HYSTERESIS limit of 600 is set below the setpoint.  The relay closes when the reading reaches a lower limit (i.e., the setpoint less hysteresis) and opens when the reading reaches an upper limit (i.e., the setpoint).  One application of wide hysteresis is automatic tank filling.  A fill operation is automatically initiated when the tank level reaches a lower level and is terminated when the level reaches an upper limit

    

Hysteresis can be used to minimize the number of ON/OFF control cycles around a setpoint, thereby increasing the life of motors, relays, etc.  A narrow hysteresis band—such as the 5 counts shown in the above figure—can also be used to minimize relay chatter around a setpoint due to electrical noise on the signal, or to signal feedback caused by load switching.  In this case, the hysteresis limit should exceed the noise amplitude.

Relay action may be derived from the filtered measurement signal, to reduce the chance of alarm triggering due to noise.  Or it may be selected to operate from the unfiltered signal, to achieve the fastest response time (typically 17 ms for a Digital Panel Meter with the solid-state relay board).

Relay chatter from signal noise can also be reduced by activating a programmable time delay (1 to 128 readings, corresponding to 20 ms to 2 s) prior to updating the output.  Snubber circuitry in the relay board helps prolong contact life.  The relay response time of counter meters is controlled by a selectable gate time from 10 ms to 199.99 s.

Dual Controller Specifications  [Top ]

Basic

Power

Provided by basic meter

Update Rate

60 Hz or 50 Hz

Setup

Setpoint values may be entered via front-panel push buttons or optional RS232/RS485 interface

Lockouts

Front-panel push buttons can control both display and change of setpoints, or display of setpoints only—or they can be completely disabled

Output Operation

Either output may be set to operate above, below, or around the setpoint (via band deviation or hysteresis mode), latching or nonlatching—or it may be disabled

Filtering

Comparison to setpoints may be either from the filtered or unfiltered input signal

Time Delay

Selectable time delay of output status change (from 1 to 128 readings)

Hysteresis

Selectable from 0 to +99999 counts

Alarm Status Indicators

Type

2 red LED lamps; each lamp is lit when the corresponding relay is energized

Contact Relay Output ("A" Option)

Power Rating

AC Load

10 A at 250 VAC

DC Load

8 A at 24 VDC

Isolation to Signal and Meter Ground

Group

C

Rated Voltage

259 VAC

Withstand Voltage

4.2 kV peak for 1 min.

Response Time to Input Signal

Pickup (for DPM)

26 milliseconds, typical (unfiltered)

Release (for DPM)

22 milliseconds, typical (unfiltered)

Pickup or Release (for Counter Meter)

Gate time + 30 mx + 2 periods max.

Solid-State Relay Output ("B" Option)

Power Rating

AC Load

120 mA at 125 VAC, 20 Ω series resistance

DC Loads

2 loads: 250 mA, 0-150 VDC peak holdoff, 5 Ω series resistance
4 loads: 120 mA, 0-150 VDC peak holdoff, 10 Ω series resistance

Isolation to Signal and Meter Ground

Type

Optical

Safety Rating

250 VAC, 4.2 kV peak per high-voltage test

Response Time to Input Signal

For DPM

17 milliseconds, typical (unfiltered)

For Counter Meter

Gate time + 30 mx + 2 periods max.

[Top ]

  

© 1996, 2002 Daytronic Corporation