Model
10AAO-8 Analog Output Card
[Back
] |
This
card provides up to eight independent, digitally-controlled analog output
signals that can be used for commanding servo control loops, and for
driving external recorders, plotters, indicators, etc.
The
eight voltage outputs are individually controlled and updated once each
scan cycle by the system Central Processor, in accordance with user or
computer instructions.
The
data source for each 10AAO-8 output may be specified as a linear function
of any system data channel No. y by applying an ANALOG
OUTPUT (ANO) command of
ANO
x = m(CHN y) + b
where
"m" and "b" are floating-point constants entered by
the user to convert the engineering units of Channel No. y to millivolts.
The allowable range is ±5000 mV. Alternatively, the data source for
an analog output may be specified as a fixed millivolt value
("e"), through a command of
ANO
x = e
For
conversion of one or more 10AAO-8 outputs to standard 4-20 mA
signals or to ±10 VDC, see the Model 10CAI-8
(below); for generation of isolated ±10 VDC outputs, see the Model
10CISO-8 (below).
Click
here for analog output channel "type codes."
Model
10AAO-8 Specifications [Top
] |
|
Voltage
Signal Outputs |
|
Configuration |
Single-ended,
return to System Common |
|
Range |
±5
volts, with 20% overrange
|
|
Resolution |
Settable
to 1 mV |
|
Allowable
Loading |
5
mA, maximum |
|
Accuracy |
±0.05%,
±1 mV
|
|
Response
Time |
Output
updated once each scan cycle, and processed through 3-pole, 4-Hz
active filter (settling time 300 milliseconds)*; scan cycles per
second= 2500/(N + 15), where N is total number of channels |
|
*
Higher filter values (1 kHz, 2 kHz, or higher) are available on
specially modified versions of the 10AAO-8 (contact
the factory for details). |
Model
10AAO-4 Analog Buffer Card
[Back
] |
For
purposes of "real-time" monitoring, the Model 10AAO-4 provides
continuous buffering, filtering, and fixed gain of 1, 2, or 4 for
up to four individual System 10 analog signals. Each signal may
originate from any system Conditioner Card
that
provides "AUXILIARY
OUTPUT" to wire-wrap pins on the mainframe's Analog
Motherboard.* The actual gain setting for each output will depend on
the "TYPE" code of
the corresponding "source" conditioner channel.
Each
of the 10AAO-4's four outputs is nominal ±5 VDC (±6 V maximum), with a
minimum load resistance of 2 kΩ. Each output is factory-set for
a "single-ended" configuration—i.e., output referenced to
Signal Common (Ground). If desired, however, all four outputs may be
reconfigured as "floating," by connecting an external supply of
±9 VDC, furnished by the user.
Each
10AAO-4 channel contains a 3-pole modified Butterworth filter with a
bandwidth of 47 Hz. In addition, individual ZERO and SPAN controls
are accessible at the front of the card, for further calibration or
scaling of a given channel with reference to its "source" input.
For
conversion of one or more 10AAO-4 outputs to standard 4-20 mA
signals or to ±10 VDC, see the Model 10CAI-8
(below); for generation of isolated ±10 VDC outputs, see the Model
10CISO-8 (below).
*
The following cards do not produce "Auxiliary Output" and may
therefore not be directly connected to the Model 10AAO-4 without special
modification: 10A9-8C, 10A10-4, 10A15-8, 10A35, 10A62-8, 10A64-8C,
10A65-8, and 10A69-4.
Model
10CISO-8 Isolated Analog Buffer Interface [Back
] |
The
Model 10CISO-8 is an external unit for ±10-V isolated buffering of up to
eight individual analog signals (with 20% overrange at 1 mA and minimum
load resistance of 2.5 kΩ). Common-mode range for the 10CISO-8 is ±50
V, with a rejection ratio of -46 dB at DC and at 60 Hz.
The
10CISO-8 may be used to amplify the standard ±5-V
analog outputs of a Model 10AAO-8 or Model
10AAO-4, or of a Conditioner
Card that issues such output. A six-foot power cord comes
with every unit, with a switch-selectable transformer that may be plugged
into any standard source of 110 or 220 VAC. Model 10CISO-8
dimensions (HWD in inches/cm) are 1.14/2.90, 9.05/22.99, 3.25/8.26.
Model
10CAI-8 Buffer Interface [Back
] |
Using
this externally mounted buffer unit with the Model 10AAO-8 or Model
10AAO-4, you can directly connect system analog outputs to a test
or process that employs ISA standard 4-20 mA control signals, or
you can amplify analog outputs to the ±10 VDC range.
Receiving
up to eight standard ±5-V inputs from the 10AAO-8 or 10AAO-4, the 10CAI-8
produces up to eight corresponding output signals, each of which is
individually programmable for full-scale representation as
 |
4
to 20 mA (corresponding to a 10AAO-8 or 10AAO-4 output of 0 to
+5 VDC) |
 |
4
to 12 to 20 mA ("zero-center," corresponding to a -5
to +5 VDC output) |
 |
±10
VDC (corresponding to a -5 to +5 VDC output) |
All
10CAI-8 outputs are "single-ended," and return to Signal Common.
A
six-foot power cord comes with every unit, with a switch-selectable
transformer that may be plugged into any standard source of 110 or 220 VAC.
Model 10CAI-8 dimensions (HWD in inches/cm) are 1.14/2.90, 9.05/22.99,